• Open frame type for direct PCB mounting • Input voltage range: 85...264V AC • Overload protection, shutdown, reset: auto recovery • Short-circuit proof • Isolation Class II • For medical usage, EN60601-1 compliant • Low standby current consumption 0,5W
|
 |
 |
|
|
Operating Temperature:
|
-20...+70°C
|
Storage Temperature:
|
-40...+85°C
|
Overload Protection:
|
>105%
|
Overvoltage:
|
115...135%
|
Insulation Voltage
|
I/P-O/P:
|
4000V AC
|
Insulation Resistance (I/P-O/P: 500V DC):
|
100MW
|
Hold Up Time (230V):
|
100ms
|
Weight:
|
30g
|
I/P = Input, O/P = Output, FG = Frame Ground
|
 |
 |
|
|
Input Voltage:
|
85...264V AC (47...440Hz)
|
120...370V DC
|
AC Current (230V):
|
0,08A
|
In-Rush Current, Cold Start (230V):
|
45A
|
 |
|
|
|
|
|
|
|
|
Part Nr.
|
UA
|
DUA
|
IAN
|
IA
|
PA
|
URW
|
h
|
| |
[V]
|
[%]
|
[A]
|
[A]
|
[W]
|
[mVp-p]
|
[%]
|
| NFM-05-3,3 |
3,3
|
2
|
1,25
|
0...1,25
|
4,12
|
80
|
67
|
| NFM-05-5 |
5
|
2
|
1,00
|
0...1,00
|
5,00
|
80
|
71
|
| NFM-05-12 |
12
|
1
|
0,42
|
0...0,42
|
5,04
|
150
|
73
|
| NFM-05-15 |
15
|
1
|
0,33
|
0...0,33
|
4,95
|
150
|
74
|
| NFM-05-24 |
24
|
1
|
0,23
|
0...0,23
|
5,52
|
240
|
76
|
UA = Output Voltage, DUA = Output Voltage Tolerance, IAN = Output Rated Current, IA = Output Current Range, PA = DC Output Power, URW = Ripple & Noise, h = Efficiency
|
 |
|